PM-TT1X

Thermocouple Converter with Isolated Input and Selectable Analogue Output PM-TT1X

The PM-TT1X is a single-channel thermocouple transmitter with an isolated input. It supports J, K, T, E, N, R, S and B thermocouples, provides cold-junction compensation and converts measured temperature to a selectable analogue output: 4–20 mA, 0–20 mA, 0–10 V or 0–5 V. Digital readings are also available over RS485 with Modbus RTU.

  • RS485 communication
  • Modbus RTU communication
  • Isolation
  • Supports J, K, T, E, N, R, S and B thermocouples
  • Isolated thermocouple input helps reduce the effects of electrical noise and ground loops
  • Selectable 4–20 mA, 0–20 mA, 0–10 V or 0–5 V output
  • Cold-junction compensation (CJC) from an internal sensor near the thermocouple input
  • RS485 communication with Modbus RTU; baud rates from 2,400 to 230,400

18-month warranty

Device specifications

Technical specifications

Controller type
Temperature
Input type
Thermocouple: J, K, T, E, N, R, S and B
Number of inputs
1 isolated input
Sensor temperature range
−200 to +1,850 °C
Analogue-to-digital converter
19 bit
Cold-junction compensation
Internal sensor (CJC)

Electrical specifications

Power supply
24 VDC
Analogue output
4–20 mA, 0–20 mA, 0–10 V or 0–5 V
Digital-to-analogue converter resolution
14 bit; 16,384 points

Indicators and configuration

Keypad
Yes
Configuration switches
Yes
Indicator LEDs
Power and Status

Mechanical specifications

Dimensions
99 × 23 × 111 mm
Housing material
Compact plastic
Mounting
DIN rail
Wiring connection
Connector
Operating temperature
−30 to +75 °C
Module operating temperature
−30 to +75 °C

Serial communication

Serial communication
Yes
Serial interface
RS485
Communication protocol
Modbus RTU
Baud rate
2,400 to 230,400

About PM-TT1X Thermocouple Converter with Isolated Input and Selectable Analogue Output

PM-TT1X single-channel thermocouple transmitter

The PM-TT1X accepts one thermocouple input and converts the measured temperature into a linear analogue signal. It supports J, K, T, E, N, R, S and B thermocouples. Use the DIP switches to select the sensor type and the lower and upper limits of the analogue temperature scale.

Thermocouple ranges are digitally calibrated at the factory, and the calibration coefficients are stored in the transmitter. The input is read at 19-bit resolution. An internal sensor near the input terminals provides cold-junction compensation (CJC). The overall sensor range stated on the product page is −200 to +1,850 °C; the usable range depends on the thermocouple type and the selected analogue scale limits.

The thermocouple input is isolated from the other circuit sections to help reduce the effects of electrical noise and ground loops on measurement. Isolation does not replace correct wiring, suitable earthing or the installation instructions.

Select one of four analogue outputs with the DIP switches: 4–20 mA, 0–20 mA, 0–10 V or 0–5 V. A 14-bit digital-to-analogue converter (DAC) generates the output in proportion to measured temperature. The source specification states an output resolution of 16,384 points.

For digital connection to a PLC, HMI or computer, the PM-TT1X supports Modbus RTU over RS485 at configurable baud rates from 2,400 to 230,400.

Selecting the sensor type and output

Use the DIP switches to select the thermocouple type, lower and upper analogue scale limits, and output signal to match the receiving controller. For an analogue connection, check that the PLC or controller accepts the selected signal type and range. Use RS485 with Modbus RTU when reading data over the serial network.

Choose a model by sensor type and channel count

For four thermocouple inputs, see the four-channel PM-TT4K. For several PT100 measurement points, compare the PM-TT4R four-channel transmitter. For a single PT100 measurement point, see the PM-TT1R.

Frequently asked questions about the PM-TT1X

Which thermocouple types does the PM-TT1X support?

The product page lists J, K, T, E, N, R, S and B thermocouples. Select the sensor type with the DIP switches. Confirm the supported types against the product manual before specifying the unit.

Which analogue outputs are available?

The selectable outputs are 4–20 mA, 0–20 mA, 0–10 V and 0–5 V. DIP switches set the output type and lower and upper limits of the temperature scale.

How does cold-junction compensation (CJC) work?

An internal sensor near the thermocouple input measures the reference-junction temperature for cold-junction compensation.

Is the thermocouple input isolated?

Yes. The thermocouple input is isolated from the other circuit sections to help reduce the effects of electrical noise and ground loops on the measurement.

How does the PM-TT1X connect to a PLC or HMI?

Connect through a compatible analogue input or use RS485 with Modbus RTU. Check the communication settings in the product manual.

What are the sensor and module temperature ranges?

The product page states an overall sensor range of −200 to +1,850 °C and a module operating range of −30 to +75 °C. The usable measurement limits depend on the thermocouple type and configured scale.

Can the PM-TT1X measure at several points?

No. The PM-TT1X has one thermocouple input. For four thermocouple inputs, see the PM-TT4K.

PM-TT1X dimensions

Reference enclosure drawing. See the specifications table for the current enclosure dimensions.

PM-TT1X thermocouple transmitter dimensions